LOK16系列燃油燃烧器控制器(SIEMENS)


LOK16系列燃油燃烧器控制器

品牌:SIEMENS(西门子)

产地:德国

产品介绍

Burner controls type LOK16... feature a self-checking flame supervision circuit. That supervision circuit initiates the required safety actions not only in the case of premature or missing flame signals, but also in the event of any kind of fault on the flame detector, the detector cables or the flame signal amplifier that could simulate a flame signal during burner operation.

The burner controls are therefore suited for use in all types of oil-fired combustion plants where self-checking flame supervision systems are either mandatory or recommendable:

  • Burners that operate continuously

  • Burners in intermittent operation that, in the case of great heat demand, may operate continuously for more than 14 hours, e.g. in plants using boiler sequencing

  • Burners that need to comply with the German TRD 411 and TRD 412 regulations for steam boilers

  • Burners in plants where, for specific safety requirements, supervision of the burner by a self-checking flame supervision system seems advisable

型号表
 LOK16.140A27LOK16.250A27LOK16.650A27注释
快速式通用式重油式
t11022.567.5预吹扫时间(风门全开时)
TSA455安全时间
TSA’---安全时间
t322.52.5预点火时间
t3’从启动命令开始(如果带有空气压力监测,从接受到空气压力监控信号开始)长预点火时间
t3n101515后点火时间(点火变压器连接端口15
t487.57.5TSA开始到端口19的阀打开的间隔时间
t4’---TSA开始到端口19的阀打开的间隔时间
t547.57.5t4结束到比例调节或端口20的阀门打开的间隔时间
t6101515后吹扫时间
t722.52.5打开风机马达2的延迟时间
t83047.592.5没有t11t12时,整个启动阶段时间
t9---第二安全时间
t1061010从启动到空气压力监测开始工作的间隔时间
t11Optional风门打开到最大位置的时间
t12Optional风门至小火位置的时间
t13


可允许的燃烧后时间
t16455从启动到风门打开命令的间隔时间
t20323512.5锁定后程序内部循环时间
类似型号LAL2.14LAL2.25LAL2.65
技术参数
主要参数
主电压AC220V -15%...AC240V +10%
AC100V -15%...AC110V +10%
主频率50...60Hz ±6%
外部保险丝16A
功率3.5VA
重量1000g(底座165g
保护等级IP40
环境条件
运输环境IEC 60 721-3-2
内部条件class 2K2
温度范围-50...+60ºC
机械条件class 2M2
湿度<95%
运行环境IEC 60 721-3-3
内部条件class 3K5
机械条件class 3M2
温度范围-20...+60&ordm;C
湿度<95%
不得进水